6.1 MODULE 1 - S IGNAL I NPUT P ARAMETERS ( 1-INP )
1-INP
SEL
PARAMETER MENU
Pro
tYPE
RTD Type
SCALE
Temperature
dECPt
Display
OFSEt
Display Offset
FILtr
Filter Setting
bANd
Filter Band
USrIN
User Input
U-ASN
User Input
Scale
Decimal Point
Value
Function
Assignment
?
tYPE
?
?
Pt385
SELECTION
Pt385
Pt392
Ni672
Cu427
RTD TYPE
TYPE
RTD Platinum 385
RTD Platinum 392
RTD Nickel 672
RTD Copper 10 ?
RANGE JUMPERS
100 ohm
100 ohm
100 ohm
10 ohm
FILTER BAND
bANd ?
00 to 199 display units
10
The filter will adapt to variations in the input signal. When the variation
exceeds the input filter band value, the filter disengages. When the variation
becomes less than the band value, the filter engages again. This allows for a
Select the RTD type used for the application. The appropriate curve will be
automatically loaded for the selected type. The position of the Input Range
Jumper must match the RTD type selected.
stable readout, but permits the display to settle rapidly after a large process
change. The value of the band is in display units, independent of the Display
Decimal Point position. A band setting of ‘0’ keeps the filter permanently
engaged at the filter level selected in the previous parameter.
?
TEMPERATURE SCALE
SCALE ?
°F °C
°F
Select the temperature scale. This selection applies for the Input, MAX and
MIN displays.
USrIN
?
DISPLAY
?
NO
MODE
USER INPUT FUNCTION
DESCRIPTION
NO
P-Loc
No Function
Program Mode Lock-out
User Input disabled.
See Programming Mode Access chart
(Module 3).
dECPt
?
?
0
DISPLAY DECIMAL POINT
0 0.0
rESEt
d-HLd
Reset (Edge triggered)
Display Hold
Resets the assigned value(s) to the
current input value.
Holds the assigned display, but all other
meter functions continue as long as
activated (maintained action).
Select the decimal point location for the desired display resolution. This
selection applies for the Input, MAX and MIN displays.
DISPLAY OFFSET VALUE
OFSEt ? -19999 to 19999
? 0
The temperature display can be corrected with an offset value. This can be
used to compensate for probe errors, errors due to variances in probe placement
or adjusting the readout to a reference thermometer.
d-SEL
d-LEV
COLOr
Print
P-r5t
rSt-1
rSt-2
rSt12
Display Select
(Edge Triggered)
Display Intensity Level
(Edge Triggered)
Backlight Color
(Edge Triggered)
Print Request
Print and Reset
Setpoint 1 Reset
Setpoint 2 Reset
Setpoint 1 and 2 Reset
Advance once for each activation.
Increase intensity one level for each
activation (backlight version only).
Change backlight color with each
activation (backlight version only).
Serial transmit of the active parameters
selected in the Print Options menu
(Module 5).
Same as Print Request followed by a
momentary reset of the assigned value(s).
Resets setpoint 1 output.
Resets setpoint 2 output.
Reset both setpoint 1 and 2 outputs.
?
FILTER SETTING
FILtr ?
0,1 2 3
1
If the displayed temperature is difficult to read due to small process
variations or noise, increased levels of filtering will help to stabilize the display.
Software filtering effectively combines a fraction of the current input reading
with a fraction of the previous displayed reading to generate the new display.
Filter values represent no filtering (0), up to heavy filtering (3). A value of 1
for the filter uses 1/4 of the new input and 3/4 of the previous display to
generate the new display. A filter value of 2 uses 1/8 new and 7/8 previous. A
filter value of 3 uses 1/16 new and 15/16 previous.
7
USER INPUT ASSIGNMENT
U-ASN ? HI          HI-LO
? dSP LO dSP
Select the value(s) to which the User Input Function is assigned. The User
Input Assignment only applies if a selection of reset, display hold, or print and
reset is selected in the User Input Function menu.
相关PDF资料
CUB5TCB0 METER PANEL LCD THERMOCOUPLE RED
CUB5USB0 USB OPTION CARD
CUB5VR00 METER LCD DC VOLT 8DIGIT
CUR-3285-MB BOX ABS 8.25X5.15X3.13" BLACK
CUR-3286-MB BOX ABS 10.15X6.15X3.13" BLACK
CUR-793-MB BOX ABS 4.1" X 2.23" X 2" W/BKTS
CUSTOM BGA CUSTOM BGA SOCKETS
CW2500 EPOXY OVERCOAT 0.26OZ
相关代理商/技术参数
CUB5SNK0 功能描述:DUAL SINKING OPEN OC OUT CARD RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5TB00 功能描述:TIMER & CYCLE COUNTER W/BKLT RoHS:是 类别:工业控制,仪表 >> 计数器 系列:* 其它有关文件:Declaration of Conformity 标准包装:1 系列:99766 计数速率:25Hz 数字/字母数:5 输入类型:机电式脉冲 输出类型:- 电源电压:24V 显示器类型:十进制拨轮
CUB5TCB0 功能描述:METER PANEL LCD THERMOCOUPLE RED RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:CUB5 标准包装:12 系列:* 其它名称:Q7072030
CUB5TCR0 功能描述:THERMO METER REFLECTIVE RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5TR00 制造商:Red Lion Controls 功能描述:PRESET TIMR & CYCLE COUNTR W/REFL DSPLY 制造商:Red Lion Controls 功能描述:TIMER, ELECTRONIC , 8DIGIT, 9V TO 28V; Supply Voltage Range:9V DC to 28V DC; Panel Cutout Height:39.1mm; Panel Cutout Width:74.9mm; Time Range:- ;RoHS Compliant: Yes
CUB5USB0 功能描述:USB OPTION CARD RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5VB00 功能描述:DC VOLTMETER RED/GREEN BKLT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030
CUB5VR00 功能描述:METER LCD DC VOLT 8DIGIT RoHS:是 类别:工业控制,仪表 >> 仪表 - 面板,数字 系列:* 标准包装:12 系列:* 其它名称:Q7072030